Filtered by vendor Rockwellautomation
Subscribe
Total
352 CVE
| CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
|---|---|---|---|---|---|
| CVE-2024-7960 | 1 Rockwellautomation | 1 Pavilion8 | 2026-06-17 | N/A | 9.1 CRITICAL |
| The Rockwell Automation affected product contains a vulnerability that allows a threat actor to view sensitive information and change settings. The vulnerability exists due to having an incorrect privilege matrix that allows users to have access to functions they should not. | |||||
| CVE-2024-7847 | 1 Rockwellautomation | 4 Rslogix 5, Rslogix 500, Rslogix Micro Developer and 1 more | 2026-06-17 | N/A | 7.7 HIGH |
| VULNERABILITY DETAILS Rockwell Automation used the latest versions of the CVSS scoring system to assess the following vulnerabilities. The following vulnerabilities were reported to us by Sharon Brizinov of Claroty Research - Team82. A feature in the affected products enables users to prepare a project file with an embedded VBA script and can be configured to run once the project file has been opened without user intervention. This feature can be abused to trick a legitimate user into executing malicious code upon opening an infected RSP/RSS project file. If exploited, a threat actor may be able to perform a remote code execution. Connected devices may also be impacted by exploitation of this vulnerability. | |||||
| CVE-2024-7515 | 1 Rockwellautomation | 12 Compact Guardlogix 5380 Sil 2, Compact Guardlogix 5380 Sil 2 Firmware, Compact Guardlogix 5380 Sil 3 and 9 more | 2026-06-17 | N/A | 7.5 HIGH |
| CVE-2024-7515 IMPACT A denial-of-service vulnerability exists in the affected products. A malformed PTP management packet can cause a major nonrecoverable fault in the controller. | |||||
| CVE-2024-7513 | 1 Rockwellautomation | 1 Factorytalk View | 2026-06-17 | N/A | 8.8 HIGH |
| CVE-2024-7513 IMPACT A code execution vulnerability exists in the affected product. The vulnerability occurs due to improper default file permissions allowing any user to edit or replace files, which are executed by account with elevated permissions. | |||||
| CVE-2024-7507 | 1 Rockwellautomation | 12 Compact Guardlogix 5380 Sil 2, Compact Guardlogix 5380 Sil 2 Firmware, Compact Guardlogix 5380 Sil 3 and 9 more | 2026-06-17 | N/A | 6.5 MEDIUM |
| CVE-2024-7507 IMPACT A denial-of-service vulnerability exists in the affected products. This vulnerability occurs when a malformed PCCC message is received, causing a fault in the controller. | |||||
| CVE-2024-6436 | 1 Rockwellautomation | 1 Sequencemanager | 2026-06-17 | N/A | 6.5 MEDIUM |
| An input validation vulnerability exists in the Rockwell Automation Sequence Manager™ which could allow a malicious user to send malformed packets to the server and cause a denial-of-service condition. If exploited, the device would become unresponsive, and a manual restart will be required for recovery. Additionally, if exploited, there could be a loss of view for the downstream equipment sequences in the controller. Users would not be able to view the status or command the equipment sequences, however the equipment sequence would continue to execute uninterrupted. | |||||
| CVE-2024-6435 | 1 Rockwellautomation | 1 Pavilion8 | 2026-06-17 | N/A | 8.8 HIGH |
| A privilege escalation vulnerability exists in the affected products which could allow a malicious user with basic privileges to access functions which should only be available to users with administrative level privileges. If exploited, an attacker could read sensitive data, and create users. For example, a malicious user with basic privileges could perform critical functions such as creating a user with elevated privileges and reading sensitive information in the “views” section. | |||||
| CVE-2024-6326 | 1 Rockwellautomation | 2 Factorytalk Policy Manager, Factorytalk System Services | 2026-06-17 | N/A | 5.5 MEDIUM |
| An exposure of sensitive information vulnerability exists in the Rockwell Automation FactoryTalk® System Service. A malicious user could exploit this vulnerability by starting a back-up or restore process, which temporarily exposes private keys, passwords, pre-shared keys, and database folders when they are temporarily copied to an interim folder. This vulnerability is due to the lack of explicit permissions set on the backup folder. If private keys are obtained by a malicious user, they could impersonate resources on the secured network. | |||||
| CVE-2024-6325 | 1 Rockwellautomation | 1 Factorytalk Policy Manager | 2026-06-17 | N/A | 6.5 MEDIUM |
| The v6.40 release of Rockwell Automation FactoryTalk® Policy Manager CVE-2021-22681 https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.PN1550.html and CVE-2022-1161 https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.PN1585.html by implementing CIP security and did not update to the versions of the software CVE-2022-1161 https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.PN1585.html and CVE-2022-1161. https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.PN1585.html | |||||
| CVE-2024-6207 | 1 Rockwellautomation | 16 Compact Guardlogix 5380 Sil 2, Compact Guardlogix 5380 Sil 2 Firmware, Compact Guardlogix 5380 Sil 3 and 13 more | 2026-06-17 | N/A | 7.5 HIGH |
| CVE 2021-22681 https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.PN1550.html and send a specially crafted CIP message to the device. If exploited, a threat actor could help prevent access to the legitimate user and end connections to connected devices including the workstation. To recover the controllers, a download is required which ends any process that the controller is running. | |||||
| CVE-2024-6089 | 1 Rockwellautomation | 2 5015-aenftxt, 5015-aenftxt Firmware | 2026-06-17 | N/A | 7.5 HIGH |
| An input validation vulnerability exists in the Rockwell Automation 5015 - AENFTXT when a manipulated PTP packet is sent, causing the secondary adapter to result in a major nonrecoverable fault. If exploited, a power cycle is required to recover the product. | |||||
| CVE-2024-6077 | 1 Rockwellautomation | 14 1756-en4, 1756-en4 Firmware, Compact Guardlogix 5380 Sil 2 and 11 more | 2026-06-17 | N/A | 7.5 HIGH |
| A denial-of-service vulnerability exists in the Rockwell Automation affected products when specially crafted packets are sent to the CIP Security Object. If exploited the device will become unavailable and require a factory reset to recover. | |||||
| CVE-2024-5990 | 1 Rockwellautomation | 2 Thinmanager, Thinserver | 2026-06-17 | N/A | 7.5 HIGH |
| Due to an improper input validation, an unauthenticated threat actor can send a malicious message to a monitor thread within Rockwell Automation ThinServer™ and cause a denial-of-service condition on the affected device. | |||||
| CVE-2024-5989 | 1 Rockwellautomation | 2 Thinmanager, Thinserver | 2026-06-17 | N/A | 9.8 CRITICAL |
| Due to an improper input validation, an unauthenticated threat actor can send a malicious message to invoke SQL injection into the program and cause a remote code execution condition on the Rockwell Automation ThinManager® ThinServer™. | |||||
| CVE-2024-5988 | 1 Rockwellautomation | 2 Thinmanager, Thinserver | 2026-06-17 | N/A | 9.8 CRITICAL |
| Due to an improper input validation, an unauthenticated threat actor can send a malicious message to invoke a local or remote executable and cause a remote code execution condition on the Rockwell Automation ThinManager® ThinServer™. | |||||
| CVE-2024-5659 | 1 Rockwellautomation | 12 1756-en4, 1756-en4 Firmware, Compact Guardlogix 5380 and 9 more | 2026-06-17 | N/A | 6.5 MEDIUM |
| Rockwell Automation was made aware of a vulnerability that causes all affected controllers on the same network to result in a major nonrecoverable fault(MNRF/Assert). This vulnerability could be exploited by sending abnormal packets to the mDNS port. If exploited, the availability of the device would be compromised. | |||||
| CVE-2024-4609 | 1 Rockwellautomation | 1 Factorytalk View | 2026-06-17 | N/A | 9.8 CRITICAL |
| A vulnerability exists in the Rockwell Automation FactoryTalk® View SE Datalog function that could allow a threat actor to inject a malicious SQL statement if the SQL database has no authentication in place or if legitimate credentials were stolen. If exploited, the attack could result in information exposure, revealing sensitive information. Additionally, a threat actor could potentially modify and delete the data in a remote database. An attack would only affect the HMI design time, not runtime. | |||||
| CVE-2024-45826 | 1 Rockwellautomation | 1 Thinmanager | 2026-06-17 | N/A | 6.8 MEDIUM |
| CVE-2024-45826 IMPACT Due to improper input validation, a path traversal and remote code execution vulnerability exists when the ThinManager® processes a crafted POST request. If exploited, a user can install an executable file. | |||||
| CVE-2024-45825 | 1 Rockwellautomation | 2 5015-u8ihft, 5015-u8ihft Firmware | 2026-06-17 | N/A | 7.5 HIGH |
| CVE-2024-45825 IMPACT A denial-of-service vulnerability exists in the affected products. The vulnerability occurs when a malformed CIP packet is sent over the network to the device and results in a major nonrecoverable fault causing a denial-of-service. | |||||
| CVE-2024-45824 | 1 Rockwellautomation | 1 Factorytalk View | 2026-06-17 | N/A | 9.8 CRITICAL |
| CVE-2024-45824 IMPACT A remote code vulnerability exists in the affected products. The vulnerability occurs when chained with Path Traversal, Command Injection, and XSS Vulnerabilities and allows for full unauthenticated remote code execution. The link in the mitigations section below contains patches to fix this issue. | |||||