Total
394939 CVE
| CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
|---|---|---|---|---|---|
| CVE-2013-2806 | 1 Rockwellautomation | 1 Rslinx Enterprise | 2026-06-16 | 7.8 HIGH | 7.5 HIGH |
| Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it calculates an incorrect value for the “End of Current Record” field. By sending a datagram to the service over Port 4444/UDP with the “Record Data Size” field modified to a specifically oversized value, the service will calculate an undersized value for the “Total Record Size.” Then the service will calculate an incorrect value for the “End of Current Record” field causing access violations that lead to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to these vulnerabilities can be found at the following Rockwell Automation security advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599 | |||||
| CVE-2013-2805 | 1 Rockwellautomation | 1 Rslinx Enterprise | 2026-06-16 | 7.8 HIGH | 7.5 HIGH |
| Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it receives a datagram with an incorrect value in the “Record Data Size” field. By sending a datagram to the service over Port 4444/UDP with the “Record Data Size” field modified to an oversized value, an attacker could cause an out-of-bounds read access violation that leads to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to this vulnerability can be found at the following Rockwell Automation Security Advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599 | |||||
| CVE-2013-2804 | 1 Softwaretoolbox | 1 Top Server | 2026-06-16 | 7.1 HIGH | N/A |
| The DNP Master Driver in Software Toolbox TOP Server before 5.12.140.0 allows remote attackers to cause a denial of service (master-station infinite loop) via crafted DNP3 packets to TCP port 20000 and allows physically proximate attackers to cause a denial of service (master-station infinite loop) via crafted input over a serial line. | |||||
| CVE-2013-2803 | 1 Prosoft-technology | 1 Radiolinx Controlscape | 2026-06-16 | 9.3 HIGH | N/A |
| ProSoft RadioLinx ControlScape before 6.00.040 uses a deficient PRNG algorithm and seeding strategy for passphrases, which makes it easier for remote attackers to obtain access via a brute-force attack. | |||||
| CVE-2013-2802 | 1 Sixnet | 2 Rtu Firmware, Udr | 2026-06-16 | 10.0 HIGH | N/A |
| The universal protocol implementation in Sixnet UDR before 2.0 and RTU firmware before 4.8 allows remote attackers to execute arbitrary code; read, modify, or create files; or obtain file metadata via function opcodes. | |||||
| CVE-2013-2801 | 1 Osisoft | 1 Pi Interface | 2026-06-16 | 5.0 MEDIUM | N/A |
| The OSIsoft PI Interface for IEEE C37.118 before 1.0.6.158 allows remote attackers to cause a denial of service (instance shutdown and data-collection outage) via crafted C37.118 configuration packets that trigger an invalid read operation. | |||||
| CVE-2013-2800 | 1 Osisoft | 1 Pi Interface | 2026-06-16 | 5.0 MEDIUM | N/A |
| The OSIsoft PI Interface for IEEE C37.118 before 1.0.6.158 allows remote attackers to cause a denial of service (memory consumption or memory corruption, instance shutdown, and data-collection outage) via crafted C37.118 configuration packets. | |||||
| CVE-2013-2798 | 1 Selinc | 4 Sel-2241, Sel-3505, Sel-3530 and 1 more | 2026-06-16 | 4.7 MEDIUM | N/A |
| Schweitzer Engineering Laboratories (SEL) SEL-2241, SEL-3505, and SEL-3530 RTAC master devices allow physically proximate attackers to cause a denial of service (infinite loop) via crafted input over a serial line. | |||||
| CVE-2013-2796 | 1 Schneider-electric | 3 Citectscada, Powerlogic Scada, Vijeo Citect | 2026-06-16 | 6.9 MEDIUM | N/A |
| Schneider Electric Vijeo Citect 7.20 and earlier, CitectSCADA 7.20 and earlier, and PowerLogic SCADA 7.20 and earlier allow remote attackers to read arbitrary files, send HTTP requests to intranet servers, or cause a denial of service (CPU and memory consumption) via an XML document containing an external entity declaration in conjunction with an entity reference, related to an XML External Entity (XXE) issue. | |||||
| CVE-2013-2794 | 1 Trianglemicroworks | 3 .net Communication Protocol Components, Ansi C Source Code Libraries, Scada Data Gateway | 2026-06-16 | 4.9 MEDIUM | N/A |
| Triangle MicroWorks SCADA Data Gateway 2.50.0309 through 3.00.0616, DNP3 .NET Protocol components 3.06.0.171 through 3.15.0.369, and DNP3 C libraries 3.06.0000 through 3.15.0000 allow physically proximate attackers to cause a denial of service (infinite loop) via crafted input over a serial line. | |||||
| CVE-2013-2793 | 1 Trianglemicroworks | 3 .net Communication Protocol Components, Ansi C Source Code Libraries, Scada Data Gateway | 2026-06-16 | 7.8 HIGH | N/A |
| Triangle MicroWorks SCADA Data Gateway 2.50.0309 through 3.00.0616, DNP3 .NET Protocol components 3.06.0.171 through 3.15.0.369, and DNP3 C libraries 3.06.0000 through 3.15.0000 allow remote attackers to cause a denial of service (infinite loop) via a crafted DNP3 TCP packet. | |||||
| CVE-2013-2792 | 1 Selinc | 4 Sel-2241, Sel-3505, Sel-3530 and 1 more | 2026-06-16 | 7.1 HIGH | N/A |
| Schweitzer Engineering Laboratories (SEL) SEL-2241, SEL-3505, and SEL-3530 RTAC master devices allow remote attackers to cause a denial of service (infinite loop) via a crafted DNP3 TCP packet. | |||||
| CVE-2013-2791 | 1 Matrikonopc | 1 Scada Dnp3 Opc Server | 2026-06-16 | 7.1 HIGH | N/A |
| MatrikonOPC SCADA DNP3 OPC Server 1.2.0 allows remote attackers to cause a denial of service (master-station daemon crash) via a malformed DNP3 TCP packet from the IP address of an outstation. | |||||
| CVE-2013-2790 | 1 Ioserver | 1 Ioserver | 2026-06-16 | 7.8 HIGH | N/A |
| The master-station DNP3 driver before driver19.exe, and Beta2041.exe, in IOServer allows remote attackers to cause a denial of service (infinite loop) via crafted DNP3 packets to TCP port 20000. | |||||
| CVE-2013-2789 | 1 Kepware | 1 Kepserverex | 2026-06-16 | 7.8 HIGH | N/A |
| The Kepware DNP Master Driver for the KEPServerEX Communications Platform before 5.12.140.0 allows remote attackers to cause a denial of service (master-station infinite loop) via crafted DNP3 packets to TCP port 20000 and allows physically proximate attackers to cause a denial of service (master-station infinite loop) via crafted input over a serial line. | |||||
| CVE-2013-2788 | 1 Subnet | 1 Substation Server | 2026-06-16 | 4.3 MEDIUM | N/A |
| The DNP3 Slave service in SUBNET Solutions SubSTATION Server 2.7.0033 and 2.8.0106 allows remote attackers to cause a denial of service (unhandled exception and process crash) via unspecified vectors. | |||||
| CVE-2013-2787 | 1 Alstom | 1 E-terracontrol | 2026-06-16 | 7.8 HIGH | N/A |
| Alstom e-terracontrol 3.5, 3.6, and 3.7 allows remote attackers to cause a denial of service (infinite loop) via crafted DNP3 packets. | |||||
| CVE-2013-2786 | 1 Alstom | 2 Micom S1 Agile, Micom S1 Studio | 2026-06-16 | 6.6 MEDIUM | N/A |
| Alstom Grid MiCOM S1 Agile before 1.0.3 and Alstom Grid MiCOM S1 Studio use weak permissions for the MiCOM S1 %PROGRAMFILES% directory, which allows local users to gain privileges via a Trojan horse executable file. | |||||
| CVE-2013-2785 | 1 Ge | 2 Intelligent Platforms Proficy Hmi\/scada Cimplicity, Intelligent Platforms Proficy Process Systems With Cimplicity | 2026-06-16 | 9.3 HIGH | N/A |
| Multiple buffer overflows in CimWebServer.exe in the WebView component in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY before 8.0 SIM 27, 8.1 before SIM 25, and 8.2 before SIM 19, and Proficy Process Systems with CIMPLICITY, allow remote attackers to execute arbitrary code via crafted data in packets to TCP port 10212, aka ZDI-CAN-1621 and ZDI-CAN-1624. | |||||
| CVE-2013-2784 | 1 Triplc | 2 Nano-10 Plc, Nano-10 Plc Firmware | 2026-06-16 | 7.8 HIGH | N/A |
| Triangle Research International (aka Tri) Nano-10 PLC devices with firmware before r81 use an incorrect algorithm for bounds checking of data in Modbus/TCP packets, which allows remote attackers to cause a denial of service (networking outage) via a crafted packet to TCP port 502. | |||||