Total
396035 CVE
| CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
|---|---|---|---|---|---|
| CVE-2014-5424 | 1 Rockwellautomation | 1 Connected Components Workbench | 2026-06-17 | 7.5 HIGH | N/A |
| Rockwell Automation Connected Components Workbench (CCW) before 7.00.00 allows remote attackers to cause a denial of service (application crash) or possibly execute arbitrary code via an invalid property value to an ActiveX control that was built with an outdated compiler. | |||||
| CVE-2014-5423 | 1 Carefusion | 1 Pyxis Supplystation | 2026-06-17 | 1.9 LOW | N/A |
| CareFusion Pyxis SupplyStation 8.1 with hardware test tool before 1.0.16 allows local users to obtain potentially sensitive information by reading a temporary (1) debugging file or (2) developer file. | |||||
| CVE-2014-5422 | 1 Carefusion | 1 Pyxis Supplystation | 2026-06-17 | 9.7 HIGH | N/A |
| CareFusion Pyxis SupplyStation 8.1 with hardware test tool before 1.0.16 has a hardcoded service password, which makes it easier for remote attackers to obtain access via unspecified vectors. | |||||
| CVE-2014-5421 | 1 Carefusion | 1 Pyxis Supplystation | 2026-06-17 | 6.8 MEDIUM | N/A |
| CareFusion Pyxis SupplyStation 8.1 with hardware test tool 1.0.16 and earlier has a hardcoded database password, which makes it easier for local users to gain privileges by leveraging cabinet access. | |||||
| CVE-2014-5420 | 1 Carefusion | 1 Pyxis Supplystation | 2026-06-17 | 3.5 LOW | N/A |
| CareFusion Pyxis SupplyStation 8.1 with hardware test tool before 1.0.16 has a hardcoded application password, which makes it easier for remote authenticated users to obtain application-file access via unspecified vectors. | |||||
| CVE-2014-5419 | 1 Ge | 14 Multilink Ml1200, Multilink Ml1200 Firmware, Multilink Ml1600 and 11 more | 2026-06-17 | 10.0 HIGH | N/A |
| GE Multilink ML800, ML1200, ML1600, and ML2400 switches with firmware 4.2.1 and earlier and Multilink ML810, ML3000, and ML3100 switches with firmware 5.2.0 and earlier use the same RSA private key across different customers' installations, which makes it easier for remote attackers to obtain the cleartext content of network traffic by reading this key from a firmware image and then sniffing the network. | |||||
| CVE-2014-5418 | 1 Ge | 14 Multilink Ml1200, Multilink Ml1200 Firmware, Multilink Ml1600 and 11 more | 2026-06-17 | 5.0 MEDIUM | N/A |
| GE Multilink ML800, ML1200, ML1600, and ML2400 switches with firmware 4.2.1 and earlier and Multilink ML810, ML3000, and ML3100 switches with firmware 5.2.0 and earlier allow remote attackers to cause a denial of service (resource consumption or reboot) via crafted packets. | |||||
| CVE-2014-5417 | 1 Meinberg | 8 Lantime M100, Lantime M200, Lantime M300 and 5 more | 2026-06-17 | 7.5 HIGH | N/A |
| Cross-site scripting (XSS) vulnerability in Meinberg NTP Server firmware on LANTIME M-Series devices 6.15.019 and earlier allows remote attackers to inject arbitrary web script or HTML via unspecified vectors. | |||||
| CVE-2014-5415 | 1 Beckhoff | 2 Embedded Pc Images, Twincat | 2026-06-17 | 9.4 HIGH | 9.1 CRITICAL |
| Beckhoff Embedded PC images before 2014-10-22 and Automation Device Specification (ADS) TwinCAT components might allow remote attackers to obtain access via the (1) Windows CE Remote Configuration Tool, (2) CE Remote Display service, or (3) TELNET service. | |||||
| CVE-2014-5414 | 1 Beckhoff | 2 Embedded Pc Images, Twincat | 2026-06-17 | 9.4 HIGH | 9.1 CRITICAL |
| Beckhoff Embedded PC images before 2014-10-22 and Automation Device Specification (ADS) TwinCAT components do not restrict the number of authentication attempts, which makes it easier for remote attackers to obtain access via a brute-force attack. | |||||
| CVE-2014-5413 | 2 Aveva, Schneider-electric | 2 Clearscada, Scada Expert Clearscada | 2026-06-17 | 6.4 MEDIUM | N/A |
| Schneider Electric StruxureWare SCADA Expert ClearSCADA 2010 R3 through 2014 R1 uses the MD5 algorithm for an X.509 certificate, which makes it easier for remote attackers to spoof servers via a cryptographic attack against this algorithm. | |||||
| CVE-2014-5412 | 2 Aveva, Schneider-electric | 2 Clearscada, Scada Expert Clearscada | 2026-06-17 | 6.4 MEDIUM | N/A |
| Schneider Electric StruxureWare SCADA Expert ClearSCADA 2010 R3 through 2014 R1 allows remote attackers to read database records by leveraging access to the guest account. | |||||
| CVE-2014-5411 | 2 Aveva, Schneider-electric | 2 Clearscada, Scada Expert Clearscada | 2026-06-17 | 4.9 MEDIUM | N/A |
| Multiple cross-site scripting (XSS) vulnerabilities in Schneider Electric StruxureWare SCADA Expert ClearSCADA 2010 R3 through 2014 R1 allow remote authenticated users to inject arbitrary web script or HTML via unspecified vectors. | |||||
| CVE-2014-5410 | 1 Rockwellautomation | 1 Ab Micrologix Controller | 2026-06-17 | 7.1 HIGH | N/A |
| The DNP3 feature on Rockwell Automation Allen-Bradley MicroLogix 1400 1766-Lxxxxx A FRN controllers 7 and earlier and 1400 1766-Lxxxxx B FRN controllers before 15.001 allows remote attackers to cause a denial of service (process disruption) via malformed packets over (1) an Ethernet network or (2) a serial line. | |||||
| CVE-2014-5409 | 1 Ge | 1 Hydran M2 | 2026-06-17 | 6.4 MEDIUM | N/A |
| The 17046 Ethernet card before 94450214LFMT100SEM-L.R3-CL for the GE Digital Energy Hydran M2 does not properly generate random values for TCP Initial Sequence Numbers (ISNs), which makes it easier for remote attackers to spoof packets by predicting these values. | |||||
| CVE-2014-5408 | 1 Nordex | 1 Nordex Control 2 Scada | 2026-06-17 | 7.5 HIGH | N/A |
| Cross-site scripting (XSS) vulnerability in the login script in the Wind Farm Portal on Nordex Control 2 (NC2) SCADA devices 15 and earlier allows remote attackers to inject arbitrary web script or HTML via the username parameter. | |||||
| CVE-2014-5407 | 1 Schneider-electric | 1 Vampset | 2026-06-17 | 4.1 MEDIUM | N/A |
| Multiple stack-based buffer overflows in Schneider Electric VAMPSET 2.2.136 and earlier allow local users to cause a denial of service (application halt) via a malformed (1) setting file or (2) disturbance recording file. | |||||
| CVE-2014-5406 | 1 Hospira | 3 Lifecare Pca3, Lifecare Pca5, Lifecare Pcainfusion Firmware | 2026-06-17 | 7.6 HIGH | N/A |
| The Hospira LifeCare PCA Infusion System before 7.0 does not validate network traffic associated with sending a (1) drug library, (2) software update, or (3) configuration change, which allows remote attackers to modify settings or medication data via packets on the (a) TELNET, (b) HTTP, (c) HTTPS, or (d) UPNP port. NOTE: this issue might overlap CVE-2015-3459. | |||||
| CVE-2014-5405 | 1 Hospira | 1 Mednet | 2026-06-17 | 9.0 HIGH | N/A |
| Hospira MedNet before 6.1 uses a hardcoded cleartext password to control SQL database authorization, which allows remote authenticated users to bypass intended access restrictions by leveraging knowledge of this password. | |||||
| CVE-2014-5403 | 1 Hospira | 1 Mednet | 2026-06-17 | 6.8 MEDIUM | N/A |
| Hospira MedNet before 6.1 uses hardcoded cryptographic keys for protection of data transmission from infusion pumps, which allows remote attackers to obtain sensitive information by sniffing the network. | |||||